| Air Filtration to Control Contamination |
| ISO 14644-1 Class | Recommended filtration |
| ISO Class 9 | Equivalent to level 1 or Pharmaceutical condition: G4 filters |
| ISO Class 8 | Production facility operating on 100% outside air: G4 and F8 filters |
| ISO Class 8 | Production facility operating on recirculated plus ambient air: where potential for product cross-contamination exists. G4,F8 &H13 filters |
| ISO Class 7 | Facility operating on recirculated air or 100% ambient air:G4,F8 & H13 filters(HEPA filters may be located terminally or in AHU) |
| ISO Class 6 | Facility operating on recirculated air or 100% ambient air:G4,F8 & H13 filters(HEPA filters to be terminally located.) |
| ISO Class 5 | Facility operating on recirculated air or 100% ambient air:G4,F8 & H13 filters(HEPA filters to be terminally located.) |
|
|
|
|
|
|
|
|
| The filter classifications referred to above relate to the EN1822 and EN779 test standards |
| which are the latest filter test standards, recommended for international use. (EN 779 relates |
| to filter classes G1 to F9 and EN 1822 relates to filter classes H10 to U16.) |